Free calculator

Size the wire for amps and distance.

Enter the load, the run length and your voltage-drop target. The calculator finds the smallest conductor that carries the load under NEC Table 310.16, then checks voltage drop and upsizes if the run is long. You see which one governs.

  • Copper & aluminum
  • 60 / 75 / 90 °C
  • 240.4(D) limits
  • Voltage drop
Electrical panel and EMT conduit runs in a commercial building under construction
Wire size calculator

Load

Phase
Conductor

Run & conditions

Recommended size
–
By ampacity
–
By voltage drop
–
Voltage drop
–

Nearby sizes

Save your results

Copy these results, then add your approved sample files in the trial brief.

Uses NEC Table 310.16 (2023), 240.4(D) and Chapter 9 Table 8 (uncoated copper, K = 12.9; aluminum K = 21.2). It does not replace the engineer of record or the code edition your AHJ enforces. Overcurrent device sizing, terminations and conduit fill are separate checks.

Reference

Copper ampacity, 75 °C column.

NEC Table 310.16: not more than three current-carrying conductors in a raceway, 30 °C ambient. 240.4(D) limits the overcurrent device for #14–#10.

Size75 °C Cu (A)75 °C Al (A)Max OCPD (240.4(D))
14 AWG20—15 A Cu
12 AWG252020 A Cu / 15 A Al
10 AWG353030 A Cu / 25 A Al
8 AWG5040—
6 AWG6550—
4 AWG8565—
2 AWG11590—
1/0150120—
4/0230180—
250 kcmil255205—
500 kcmil380310—
Method

Two checks, pick the larger.

Ampacity

Smallest size whose 310.16 ampacity, at the termination rating and after correction, carries the load (×1.25 if continuous).

Small-conductor cap

240.4(D) caps #14, #12 and #10 at 15, 20 and 30 A copper.

Voltage drop

VD = 2·K·I·L ÷ CM for single-phase, √3·K·I·L ÷ CM for three-phase, with circular mils from Chapter 9 Table 8.

Recommend

Whichever check needs the larger conductor governs.

Where RenderDraw fits

One feeder here. Every feeder in the bid.

Feeder schedules, panel schedules and one-lines drive most of an electrical estimate. RenderDraw reads them from the drawings with the source sheet on every row, so your estimator can approve wire, conduit and gear quantities before pricing.

  • Source on every row. Each proposed quantity keeps the sheet and location it came from.
  • Estimator approval before pricing. Your estimator accepts, corrects or rejects proposals; nothing is priced until it is approved.
  • Addenda through the same review. Changed sheets go back through takeoff and estimator review.
  • Your assemblies, your rates. Approved rows hand off to your assemblies, labor units and pricing inputs.
Laser distance meter measuring an empty room with a new wood floor
FAQ

Wire size calculator, answered.

What size wire do I need for 40 amps?

With copper and 75 °C terminations, 8 AWG (50 A) is the smallest that works, as long as voltage drop on the run is acceptable. Long runs may need a larger size.

What size wire for a 100 ft, 20 amp, 120 V circuit?

12 AWG copper carries 20 A, but at 100 ft one-way and a full 20 A the drop is about 7.9 V, or 6.6%. Holding 3% takes 8 AWG copper (about 3.1 V, 2.6%). Many designs check the drop at the expected load rather than the breaker rating, so use the real load.

How do you calculate voltage drop?

Single-phase: VD = 2 × K × I × L ÷ CM. Three-phase: VD = 1.732 × K × I × L ÷ CM. K is about 12.9 for copper and 21.2 for aluminum, L is the one-way length in feet and CM is the conductor's circular mils.

What voltage drop is acceptable?

The NEC's informational notes suggest about 3% for a branch circuit or feeder and 5% total to the farthest outlet. These are recommendations, not requirements, unless your spec or local code makes them mandatory.

Why use the 75 °C column?

Conductor ampacity is limited by the lowest temperature rating of the terminations. Most equipment is rated 75 °C. The 90 °C column is used as the starting point for derating, not for final sizing.

Start small

Send one plan set. Judge the result yourself.

A focused, no-obligation evaluation on your own drawings. Your sample files remain private while we assess the request.

  1. Upload one representative plan set (a legible PDF set is the most reliable starting point), plus an addendum if you have one.
  2. RenderDraw reviews the set and the scope you want tested.
  3. We follow up with what was extracted, what was flagged for review, and the most useful next step.

Book a meeting with RenderDraw

Bring your drawings, estimating process, or product configuration questions. Choose a time to talk with our team.

Prefer a separate window? Open the booking page.

Free sample takeoffCalculator