Ductwork takeoff and HVAC quantity takeoff
HVAC takeoffs start with reading the mechanical set: schedules, plans, sections, details and the duct construction spec. Ductwork is then taken off by system, size and length, fittings by type, and converted to weight or area for pricing. The spec's pressure class and sealing requirements can move the price more than the length does.
- Reading mechanical drawings
- Duct by size and length
- Fittings and weight
- Revit notes

Reading mechanical drawings, in order
- Legend and abbreviations: symbols, duct types, notes. Confirm which dimension is width.
- Equipment schedules: AHUs, RTUs, fans, VAV boxes, diffusers with sizes and CFM.
- Plans: duct routing with sizes, diffuser locations, equipment.
- Sections, risers and details: heights, drops, offsets, connections, supports.
- Specifications (Division 23): duct construction standard, pressure classes by system, sealing, materials, insulation and liner, testing.
Read the duct construction spec first
Most specs reference the SMACNA HVAC Duct Construction Standards, now ANSI/SMACNA 006-2020 (4th edition). Three things drive cost:
- Pressure class by system: ½, 1, 2, 3, 4, 6 or 10 in. w.g. Higher classes mean heavier gauge, closer reinforcement and tighter sealing.
- Seal class: SMACNA ties Class A to 4 in. w.g. and above, Class B to 3 in., and Class C to 2 in., and recommends Class C at lower pressures. Energy codes and specs often require more, so read Division 23.
- Leak testing: the 2024 IECC requires ducts designed for 3 in. w.g. and above to be tested on at least 25% of duct area to leakage class 4.0 or better. Specs may require more, including low-pressure systems.
Duct takeoff by size
| Field | Example |
|---|---|
| System | Supply, return, exhaust, outside air |
| Size | 24×12 rectangular, 12 in round, 30×12 flat oval |
| Length | LF from plan, plus risers and drops from sections |
| Pressure class | Per spec, by system |
| Material and gauge | Galvanized, stainless, aluminum; gauge from SMACNA tables |
| Insulation / liner | SF by thickness and facing |
Keep systems separate. It helps pricing, review and project tracking.
Worked example: weight of one run (illustrative)
60 LF of 24×12 supply duct, 2 in. w.g. class, assumed 24 gauge from the SMACNA tables for that size and reinforcement:
- Perimeter = 2 × (2.0 + 1.0) = 6.0 ft
- Surface area = 6.0 × 60 = 360 SF
- Weight = 360 × 1.156 lb/SF = 416 lb straight duct
- Add seams, reinforcement and waste from your own history. A blanket percentage is only a rule of thumb; heavy fittings content on short runs can add far more.
- External wrap, if required: 360 SF plus overlap, by thickness.
A branch takeoff (illustrative)
A supply branch serving four offices: 16×10 duct for 60 ft, reducing to 12×8 for 40 ft, with four 8 in round runouts of about 10 ft each, volume dampers and flex connections to diffusers.
| Item | Quantity | Unit |
|---|---|---|
| 16×10 duct | 60 | LF |
| 12×8 duct | 40 | LF |
| Reducer 16×10 to 12×8 | 1 | EA |
| 8 in round taps with volume dampers | 4 | EA |
| 8 in round duct | 40 | LF |
| Flex connections (length per spec limit) | 4 | EA |
| Diffusers | 4 | EA |
Many specs limit flex duct length at each diffuser. Check the limit before taking off long flex runs.
Fittings
Count fittings by type and size: elbows (with or without turning vanes), transitions, takeoffs, tees, offsets and end caps. For rectangular sheet metal, shops price either by weight, with fittings weighed individually or as an allowance from history, or by piece. Pick one method and use it consistently so quotes compare.
Devices and accessories
- Diffusers, registers and grilles by type, size and neck size.
- Dampers: volume, fire, smoke, combination fire/smoke, with actuators and access doors where required.
- VAV and terminal units.
- Access doors, flexible connectors, turning vanes, sound attenuators.
- Hangers and supports, per the spec and seismic requirements where they apply.
Fire and smoke dampers carry wiring, access and inspection requirements; confirm who wires actuators.
Insulation and liner
Measure external wrap by outside surface area (perimeter × length) and keep it separate by thickness and facing. Note which systems need it, typically supply and outside air in unconditioned spaces, per the energy code and spec. Lined duct is usually sized up so the inside clear dimension matches the drawing; check which dimension the drawings show.
Checks before pricing
- [ ] Sizes taken from plans, not assumed from adjacent runs.
- [ ] Vertical risers and drops included from sections and riser diagrams.
- [ ] Pressure class assigned per system.
- [ ] Dampers, access doors, turning vanes and flexible connectors counted.
- [ ] Insulation and liner taken off separately.
- [ ] Exhaust, return and outside air systems all included.
- [ ] Leak testing quantity and pressure from the spec and code.
Revit models
When a model is available, duct lengths and fittings can be scheduled from it. Check that it's complete for your scope, that fittings are modeled, and that sizes match the issued drawings.
Where RenderDraw fits
RenderDraw reads mechanical plans with schedules and specs, proposes equipment counts and duct runs with the source attached, and puts uncertain items in front of your estimator first. Your gauges, labor and pricing apply to reviewed rows only.
Equipment counts and duct runs, checked before pricing.
RenderDraw reads mechanical plans with schedules and specs, proposes equipment counts, duct and pipe runs with the source attached, and puts uncertain items in front of your estimator first.
- Equipment from schedules and plans. Traceable to the source sheet.
- Duct and pipe runs. Proposed lengths your estimator accepts or corrects.
- Addenda through the same review. Send the changed sheets back through takeoff and estimator review.
- Your labor and pricing. Applied to reviewed rows only.

Send one mechanical set
Files stay private while RenderDraw assesses the request. No obligation.
RenderDraw does not publish accuracy percentages or time-saved claims. Test it on your own plan set.
Questions estimators ask.
How do you do a ductwork takeoff?
Take off duct by system, size and length, count fittings and devices, then convert to weight (by gauge) or surface area. Add insulation or liner, accessories, hangers and any leak testing the spec or energy code requires.
How is ductwork weight calculated?
Perimeter in feet × length × weight per square foot for the gauge. Galvanized steel is about 0.906 lb/SF at 26 gauge, 1.156 at 24, 1.406 at 22, 1.656 at 20 and 2.156 at 18. Add seams, reinforcement and fittings from your own history or by taking fittings off individually.
What sets the duct gauge?
The duct size, the pressure class and the reinforcement spacing, per the SMACNA HVAC Duct Construction Standards (ANSI/SMACNA 006-2020, 4th edition) or the project spec. Don't assume one gauge for the job.
Do ducts need leak testing?
Often. The 2024 IECC requires ducts designed for 3 in. w.g. and above to be leak tested per SMACNA's test manual, on representative sections totaling at least 25% of duct area, to leakage class 4.0 or better. Many specs go further, so read Division 23.
Can I take off ductwork from Revit?
Yes, if the model is complete for your scope. Check that fittings are modeled and sizes match the drawings. Many bids still rely on PDF drawings.
Is the first duct dimension the width?
Usually the first dimension is the side shown in plan view (width) and the second is depth, but check the project legend.
Is duct lining measured separately?
Yes. Measure liner and external wrap separately by thickness and facing, by surface area, and note that lined duct is usually upsized to keep the same clear inside dimensions.
Can RenderDraw take off ductwork?
It proposes equipment counts and duct runs from mechanical drawings with the source attached, and puts uncertain items in front of your estimator first. Get a free sample takeoff at renderdraw.com/trial.
Equipment and duct runs from the mechanical set.
Send an HVAC set. RenderDraw proposes equipment counts and duct runs with sources.
- Upload the plans, specs and schedules, plus an addendum if you have one.
- RenderDraw reviews the set and the scope you want tested.
- We follow up with extracted quantities, flagged items and next steps.
Related tools and guides
Sources and further reading
- SMACNA: HVAC Duct Construction Standards – Metal and Flexible, 4th Edition (ANSI/SMACNA 006-2020)
- SMACNA technical standards
- UpCodes: IECC duct leak testing (high-pressure duct systems)
- Engineering ToolBox: sheet metal gauge weights
Figures marked as rules of thumb are starting points, not standards. Check the current edition of any code or standard your project specifies, and use your own historical production rates where you have them. Sources checked 2026-11-01.