First question: replacement or recover?
The model International Building Code (Section 1512 in the 2024 IBC, 1511 in 2021) defines roof replacement as removing all existing layers down to the deck. A recover, installing new roofing over the existing covering, is allowed in listed cases, but not where:
- the existing roof is water-soaked or deteriorated so it is not an adequate base,
- the existing covering is slate, clay, cement or asbestos-cement tile, or
- the existing roof already has two or more applications of any roof covering.
Core samples or a moisture survey (infrared, nuclear or capacitance) tell you which applies. Local amendments change details, so check the adopted code.
Energy code: the insulation upgrade nobody priced
Under the 2021 IECC (C503.2.1), a roof replacement where the existing roof has insulation entirely above the deck must meet current insulation requirements (Table C402.1.3 R-values or C402.1.4 U-factors), and insulation cannot be reduced. Recovers and repairs are generally exempt if energy use does not increase. Related provisions in the same edition:
- Continuous insulation in at least two layers with staggered joints.
- At least 1 in. of above-deck insulation at the lowest point (drain, scupper or gutter edge).
- Tapered insulation R-value calculated from average thickness.
- Cool roof requirements in climate zones 0 to 3 over cooled spaces.
Thicker insulation raises the roof surface, which can push curbs, wall flashings, edge metal, door thresholds and scuppers out of compliance. That is the hidden scope: curb extensions, taller edge metal and wood blocking, and mechanical disconnect and reset.
Scope sections
| Section | What to state |
|---|---|
| Preparation | Protection, access, hoisting, permits, fall protection, interior protection |
| Tear-off | Existing layers by type and number, insulation, disposal; asbestos survey results |
| Deck | Inspection and replacement at a unit price per sq ft or per sheet |
| New system | Manufacturer system, insulation R-value and layers, tapered design, cover board, membrane, attachment, wind uplift rating |
| Flashing | Walls, curbs, penetrations, edges, counterflashing |
| Accessories | Drains, scuppers, vents, edge metal, gutters, walkway pads |
| Closeout | Cleanup, manufacturer inspection, warranty type and term |
Flashing heights and rooftop equipment
NRCA guidance calls for base flashings at least 8 in. above the finished roof surface. After an insulation upgrade, many existing curbs and wall flashings fall short. Count every curb and record its height on the site walk; decide who disconnects, raises and resets units (usually the mechanical contractor), and say so.
Quantities
| Item | Unit | Notes |
|---|---|---|
| Roof area | SF or squares (100 SF) | True area for sloped roofs |
| Tear-off | SF by layer | Layers from cores |
| Insulation | SF by thickness; tapered by layout | Tapered layouts are often supplied by the manufacturer |
| Edge metal and coping | LF by profile | Include wood blocking raise |
| Wall flashing | LF by height | Parapets measured separately |
| Curbs and penetrations | EA by size and type | Pipes, vents, supports, conduit |
| Drains and scuppers | EA | Replace, retain or add inserts |
| Deck replacement | Unit price per SF or sheet | Quantity unknown until tear-off |
An 18,000 sq ft low-slope roof on metal deck. The bid carries 500 sq ft of deck replacement at a unit price, and the unit price applies to quantities above or below.
Without the unit price, every sheet of deck found at tear-off becomes a negotiation.
What changes the price
- Roof height, access, crane or hoist needs and material staging.
- Occupied building: noise, odor (kettles, adhesives), hours and interior protection.
- Weather and temporary waterproofing: only open as much roof as can be made watertight the same day.
- Asbestos: EPA's asbestos NESHAP requires a thorough inspection before renovation of regulated facilities; older built-up roofs, mastics and flashing cements may contain asbestos, which requires licensed abatement where present.
- Fall protection: OSHA 1926.501(b)(10) covers work on low-slope roofs; warning lines, guardrails, safety monitors and personal fall arrest each have cost.
- Wind uplift: specs may require an FM Global approval rating or ASCE 7 design pressures, which drive fastener density at corners and perimeters.
Sample scope language
"Remove existing roofing down to the structural deck, including two layers of built-up roofing and insulation, approximately 18,000 sq ft. Inspect deck and replace deteriorated metal deck at the unit price below; 500 sq ft included. Install two layers of polyisocyanurate insulation with staggered joints to the R-value required by the adopted energy code, with tapered insulation to existing drains, cover board, and fully adhered single-ply membrane. Replace edge metal and counterflashings; raise wood blocking as required. Raise curbs at RTU-1 through RTU-6 to maintain 8 in. minimum flashing height; disconnect and reset of units by others. Provide manufacturer's 20-year NDL warranty as specified."
Each phrase answers a question that otherwise becomes a dispute: how deep the tear-off goes, how deck repairs are priced, which insulation and how drainage works, what happens at edges and curbs, who moves equipment, and which warranty is included.
Common exclusions
- Structural repairs beyond the deck unit price.
- Mechanical and electrical disconnect and reconnect of rooftop equipment.
- Hazardous material abatement.
- Interior protection beyond stated measures.
- Permits, if obtained by the owner.
Where an item is likely but its quantity unknown, a unit price is more useful to both parties than an exclusion.